額定絕緣電壓
rated insulation voltage
別名:額定絕緣電壓、rated insulation voltage、Ui
額定絕緣電壓(rated insulation voltage, Ui)為製造商指派、表徵絕緣指定長期耐受能力之 RMS 耐受電壓值(IEC 61439-1 §3.8.9.3,源自 IEC 60664-1)。多相取線間電壓;不必然等於額定運轉電壓(SB-106,Note 1+2)。為決定沿面距離(SB-055,搭配污染等級 SB-062)之依據,與額定衝擊耐受電壓(SB-108,Uimp)共構絕緣協調(SB-067)。Ui ≥ Ue。
白話說明
額定絕緣電壓(Ui)是「製造商指定、絕緣能長期承受的有效值電壓」——它代表絕緣的長期耐壓能力,是決定沿面距離(爬電距離)的依據。它不一定等於工作電壓(Ue),通常 Ui ≥ Ue。
完整定義
額定絕緣電壓 Ui:由成套設備製造商指派予成套設備或其電路之 RMS 耐受電壓值,用以表徵其絕緣之指定(長期)耐受能力。
標準原文 (Original Text)
rated insulation voltage Ui RMS withstand voltage value, assigned by the assembly manufacturer (3.10.2) to the assembly or to a circuit of an assembly, characterizing the specified (long-term) withstand capability of the insulation Note 1 to entry: In polyphase circuits, it is the voltage between lines. Note 2 to entry: The rated insulation voltage is not necessarily equal to the rated operational voltage of equipment, which is primarily related to functional performance. [SOURCE: IEC 60664-1 2007, 3.9.1, modified - The symbol Ui has been added. In the definition, "manufacturer" has been replaced by "assembly manufacturer (3.10.2)" and 'equipment or to a part of it' has been replaced by 'assembly or to a circuit of an assembly'. Note 1 to entry has been added.]
額定絕緣電壓(Ui)為製造商指派、表徵絕緣「指定長期耐受能力」之 RMS 耐受電壓值(定義源自 IEC 60664-1、經修改)。多相取線間電壓(Note 1);不必然等於額定運轉電壓(Note 2)——後者主關功能性能。 絕緣協調定位:額定絕緣電壓(rated insulation voltage, SB-107,Ui)為決定沿面距離(creepage distance, SB-055)之依據(搭配污染等級, SB-062),與額定衝擊耐受電壓(SB-108,Uimp,決定間隙)共同構成絕緣協調(insulation coordination, SB-067)。Ui ≥ 額定運轉電壓(SB-106,Ue)。
生活比喻
像繩子標示的『長期安全工作張力』——不是瞬間極限,而是能長期承受的耐受值。Ui 規範絕緣的長期耐壓,配合污染等級決定要留多長的沿面距離。
為何重要
額定絕緣電壓於工程之意義:(1) 絕緣長期耐受:Ui(SB-107)為表徵絕緣指定長期耐受能力之 RMS 值;(2) 決定沿面距離:Ui 搭配污染等級(SB-062)決定沿面距離(SB-055);(3) 絕緣協調:與額定衝擊耐受電壓(SB-108,Uimp,決定間隙 SB-054)共構絕緣協調(SB-067);(4) 與運轉電壓之別(Note 2):Ui 關絕緣耐受、Ue(SB-106)關功能性能,Ui ≥ Ue。
相關連結
發現內容問題?點此回報
標準改版、翻譯錯誤、條款編號不對、缺少資訊都歡迎回報,我們會儘快修正。
發現內容問題?點此回報
標準改版、翻譯錯誤、條款編號不對、缺少資訊都歡迎回報,我們會儘快修正。