內部電弧分級
Internal Arc Classification
別名:IAC、內部電弧等級
內部電弧分級(IAC)是金屬封閉式開關設備的安全等級標示,證明該設備在內部電弧故障發生時能保護周圍人員安全。等級標示包含保護方向、電弧故障電流值和持續時間。
白話說明
金屬封閉式開關設備內部如果發生電弧故障,瞬間釋放的能量可能炸開箱體、噴出高溫氣體。IAC 分級就是透過實際試驗驗證——在指定電流和時間下發生內部電弧時,箱體不會炸開、不會噴火到操作人員站立的位置。
完整定義
經型式試驗證明在內部電弧故障發生時,能滿足規定之人員保護標準的金屬封閉式開關設備。 試驗參數包括電弧故障電流(三相及適用時單相接地)之有效值與電弧故障持續時間。
標準原文 (Original Text)
internal arc classified switchgear and controlgear (IAC): metal-enclosed switchgear and controlgear for which prescribed criteria for protection of persons are met in the event of internal arc, as demonstrated by type tests. arc fault current: three-phase (and where applicable, single phase-to-earth) r.m.s. value of the internal arc fault current for which the switchgear is designed to protect persons. arc fault duration: duration of the internal arc fault current for which the switchgear is designed to protect persons.
IAC 標示格式如 IAC-AFL 25 kA 1 s,表示: A = 受限可及性側面(Accessibility type A) F = 前方(Front) L = 側面(Lateral) R = 後方(Rear) 25 kA = 電弧故障電流 1 s = 電弧故障持續時間 試驗合格判準包含:門不得打開、外殼不得穿孔、布指示器不得著火、接地有效性維持。
生活比喻
就像汽車安全碰撞測試的星級評等——不是保證車子不會撞,而是保證撞了之後車內乘客能受到保護。IAC 分級就是開關設備的「碰撞安全星級」。
為何重要
採購金屬封閉式開關設備時,IAC 等級是保護現場操作人員的關鍵規格。人員可能站立的方向(前方、側面、後方)都必須納入保護範圍。
相關連結